Glazing Systems - 30 Minutes

Glazing Systems - 30 Minutes


Pyroplex® fire-resisting glazing systems offer a range of
solutions for glazing vision panels in fire doors.
Pyroplex® fire-resisting glazing systems are available for
30minute applications.


Pyroplex® 30minute glazing systems are fully flexible
and supplied in slimline reels for easy storage and to
minimisewastage. They are also approved for use on
slimline economical beads.


Pyroplex® fire-resisting 30minute glazing systems are
tested to BS476: Part 22: Clauses 7 & 8 and other
international standards. They are compliantwith the
requirements of CERTIFIRE TS25.


CERTIFIRE CertificateNo. CF346 & CF348.


Field of Application
Pyroplex® 30minute glazing systems have been specifically
designed for use in glazed apertures in fire doors in the following
applications:
• Glazed apertures in fire resisting timber doors and steel doors.


Product Features
• Supplied on continuous reels for dispensing applications, ease of
storage and to reducewastage in cut-offs.
• Suppliedwith a high performance self-adhesive backing for ease
of application and installation.
• Pyroplex® intumescentmaterial is totally unaffected bywater,
robust,‘non-flaking’and difficult to tear.

 

Product Data

Part Number

For Use With

Insulating Glass

For Use With

Non-Insulating Glass

30049

Yes

Yes

30054

Yes

No

8193

Yes

Yes

 


ProductTesting
Pyroplex® 30minute glazing systems have been tested to the
requirements of CERTIFIRE TS25 and other international standards,
including British Standards BS476: Part 22:1987, clause 7 & 8.


Installation Instructions
All doors must be lined with a 6mm hardwood liner around the
perimeter of the aperture. Failure to line the aperture will
invalidate the CERTIFIRE Approval.
1. Unwind the glazing system from the coil. Remove the release
liner from the product. Fit the product to the bead.
2. Mitre cut the bead (with glazing system installed) to fit the
aperture. Install one complete side of the beading system
using M5 x 50 stainless steel screws at 150mm centres.
3. Cut glass to fit aperture with a tolerance of +/-2mm and
install. Repeat steps for opposite side of the door.


Health and Safety Information
For detailed information on this product please refer to the
relevant Material Safety Data Sheet which is available on

request or downloadable at www.pyroplex.com.


Transportation & Storage
Transport Hazards: No regulations apply for the transport of this
material. Not classified as hazardous for road, rail, sea or air
transport.
Storage: Store in a cool, dry place (not above 35°C) and ensure
sufficient ventilation.


Product Guarantee
Providing the product is installed in accordance with the
requirements of the guidance document the product is
guaranteed for a period of 10 years.


Product Profiles

 

Application: Glazed apertures
Fire Resistance Period: 30 minutes
Insulation/Integrity: Insulation and Integrity
Test Standard: BS476: Part 20 and 22
Approval Type: CERTIFIRE CF346 & CF348

 

Test Reports & International Standards

CERTIFIRE CF346 & CF348

Mid-East Listing Scheme ME0042 & ME0043

Bodycote Warringtonfire 136934, 136935, 137714, 139878, 165278